Introduction
Proper installation and regular maintenance are crucial for ensuring long-term stable operation of radar level transmitters. This article provides detailed installation guidance and maintenance recommendations to help you maximize equipment performance and extend service life.
1. Pre-Installation Preparation
Site Survey: Confirm medium characteristics, process temperature/pressure, tank dimensions and material
Antenna Selection: Choose horn, rod, or parabolic antenna based on dielectric constant
Location Planning: Avoid interference sources such as inlets, agitators, and heating coils
2. Detailed Installation Steps
2.1 Flange Installation
Use matching gaskets to ensure sealing
Tighten bolts uniformly in diagonal sequence
Check flatness after installation, deviation should be <0.5°
2.2 Thread Installation
Use sealant tape or thread sealant
Avoid overtightening causing thread damage
Recommended torque: ≤60N·m for 316L stainless steel flange
2.3 Precautions
Maintain antenna perpendicular to medium surface
Minimum distance from tank wall: ≥100mm
Maintain ≥500mm spacing when installing multiple transmitters
3. Commissioning and Parameter Setting
3.1 Empty Tank Calibration
Perform empty tank learning to establish reference baseline
Set correct dielectric constant and range parameters
3.2 Echo Curve Analysis
Identify true echoes and false echoes
Use echo mapping function to mask fixed interferers
4. Preventive Maintenance Schedule
Monthly Checks:
Inspect antenna surface cleanliness
Verify output signal stability
Record deviation between measured and actual values
Quarterly Maintenance:
Clean antenna surface deposits
Check cable connector sealing
Calibrate zero and span
Annual Maintenance:
Comprehensive cleaning and calibration
Check seal aging condition
Update firmware and backup parameters
5. Common Troubleshooting
Symptom | Possible Cause | Solution |
---|---|---|
Signal Loss | Antenna contamination | Clean antenna surface |
Measurement Fluctuation | Feed interference | Adjust installation position or enable filtering |
Reading Deviation | Dielectric constant change | Recalibrate or modify parameters |
Conclusion
Following correct installation and maintenance procedures ensures radar level transmitters maintain optimal measurement performance. We recommend establishing detailed equipment records and documenting all maintenance data to build a foundation for predictive maintenance.